Instrument Transformer Division

Mobirise

Outdoor Oil Cooled Current Transformer 

APPLICATION
Direct measurement of current in High Voltage System is not possible because of insulation problem of measuring instruments. It is also not possible to use current flowing through the system directly for protection purpose due to its high value and high insulation problem.

BASIC FUNCTIONS OF CURRENT TRANSFORMERS ARE:
1. To reduce the line current to a value which is suitable     for standard measuring Instruments, relays etc.
2. To isolate the measuring instruments. Meters, relays     etc. from high voltage side of an installation,
3. To protect measuring instruments against short circuit     currents.
4. To sense abnormalities in current and give current     signals to protective relays to isolate the defective     system. 

Outdoor Oil Cooled Voltage Transformer 

APPLICATION
Direct measurement of voltage in High Voltage System is not possible because of insulation problem of measuring instruments. It is also not possible to use direct voltage for the system protection purpose due to its high value and high insulation problem of protective relays, Therefore, voltage transformers are used to step-down the high system voltage to low standard value accurately in proportion to their ratio.

BASIC FUNCTIONS OF VOLTAGE TRANSFORMERS ARE:
1. To reduce the line voltage to a value which is suitable for standard measuring instruments, relays etc.
2. To isolate the measuring instruments, meters relays etc. from high voltage side of an installation.
3. To sense abnormalities in voltage and give voltage signals to protective relays to isolate the defective system. 

Mobirise
Mobirise

Residual Voltage Transformer 

RESIDUAL VOLTAGE TRANSFORMER is used to detect unbalanced voltage in three phase system and to supply voltage to directional earth-fault relay.
For directional earth-fault relay. It is necessary that the voltage applied to voltage coil of the relay corresponds in phase to that of the current in current coil. Such voltage will be the Residual voltage of the system and will be the phasor sum of the three line-to-earth voltages.
Residual voltage can be achieved by connecting secondaries of three single phase V.Ts. connected in three phase in open-delta fashion. It is, however, economical to use three phase V.Ts. instead of Three nos. single phase V.Ts. 'AE' manufactures three phase R.V.Ts. suitable upto 33kV system voltage.
In normal three phase limb V.T. when one phase experiences earth fault, the resultant flux due to two healthy lines returns through transformer limb of faulty line, inducing a heavy short circuit current in the winding on the limb. Also voltage induced in secondary open-delta winding is not true residual voltage. To overcome this difficulty two separate limbs are provided in the magnetic circuit of three phase Voltage Transformer to form Five limb Voltage Transformer as shown in Fig. No.4
The use of an open-delta connected winding to give true residual voltage in demonstrated in Fig. No. 5 with three cases:
5A) Under healthy condition all three phases will be balanced and hence residual voltage VR will be zero.
5B) In system with unearthed neutral. if here is earth fault on one line, neutral of V.T. will be shifted, such that each healthy phase winding will have line-to-line voltage with 60° phase difference. The resultant open-delta voltage shall be therefore three times phase voltage (VR = 3 VS)
5C) In Solidly earthed system, neutral of the V.T. does not get shifted due to earth-fault one line. Therefore, the resultant open-delta residual voltage remains phase voltage only (VR = VS)
Primary winding of R.V.T. is connected in star. The secondary winding is connected in open-delta. Sometimes additional secondary winding is provided in R.V.T. for measuring purpose and is connected in Star. Ratio of R.V.T. is generally specified as line-to-line primary voltage to open-delta residual voltage. It, therefore, becomes necessary to mention system neutral condition so as to select phase voltage of the open-delta winding correctly. When R.V.Ts. are used along with Capacitor Bank capacitor bank gets discharged through primary winding 'AE' make R.V.Ts. are suitable for such applications also. 

Resin Cast CTs and PTs 

RANGE OF MANUFACTURE :
1. Tapewound ring type current Transformers with and without mounting arrangements.
2. Tapewound ring type CTs with sealing arrangements.
3. Tapewound wound primary CTs (WPL)
4. Resincast (epoxy) BPL CTs.
5. Resincast (epoxy) wound primary (WPL) CTs.
6. Bushing CTs (Fibreglass taped ). 

CORE BALANCE CTs (Resincast)
These are used in detecting earth faults of very small magnitude. A three phase cable is passed through these CTs & the unbalanced currents in the three phases set up a differential flux giving rise to a current on the secondary side of these CTs sufficient to actuate a relay.

INTERPOSING CURRENT TRANSFORMERS
( RESINCAST) :

Used in matching the ratios of main feeder CTs for differential protection schemes. These also find application as saturable CTs used in conjunction with main feeder CTs and thus protect the meters connected to these by limiting the current flowing through the meters. 

SUMMATION CTs ( RESINCAST) :-
Current transformers intedned to summate the currents in a number of feeders in association with the feeder CTs is called summation Transformer. The performance / testing of these CTs are governed by IS-6949-1973, BS-3938, IEC-185.

BUSHING CTs (FIBREGLASS TAPED) :-
Widely used by Transformer manufacturers for use in oil. 

PORTABLE CTs.
With class 0.2 accuracy for metering & testing purpose.

FURNACE CTs.
CTs. WITH ABS CASING AND WITH SEALING ARRANGEMENTS:-

Widely used by Electricity Board along with Energy meters.

LOW TENSION POTENTIAL TRANSFORMER ( TAPEWOUND I RESINCAST )
These are offered in various ratios from 1100 11101/ to 50 / 75V to suit the exact applications of the clients. Rated burdens upto 100 VA with accuracy classes of 1 or 0.5 can be offered. Various other types of low tension instruments transformers are also manufactured by us to suit the exact requirements of our clients. Our team of specialised Engineers will be pleased to be of
assistance to the clients in proper selection of instruments transformers for their applications.

PROTECTION AND CLASS PS (CLASS X) CTs.
BOTH IN TAPEWOUND / RESINCAST :

CTs, With class'PS' / class 'X' for differential protection / BUS coupler application.

The CTs I PTs manufacture by us conform to ISS 2705, BS 3938 and IEC 185-186 standards. 